Modulgroups

Addressspace

CAN NET

Driver

 

receive data

send data

 

 

Digital IO (DIO_8)

0x180 - 0x18F

0x200 - 0x20F

1

5

Analog in (CMB-AI4)

0x290 / 0x390
to
0x2FF / 0x3FF

 

1

5

ISEG HV (80V)

0x300 - 0x380

 

0

1 & 2

Siemens S5 (CSC595/2)

0x401 - 0x403

0x400

1

6

Centro Power (6V / 12V)

0x480-0x4FF

 

0

4

CMB-Board

0x500 - 0x6FF

 

1

3

Device

Addressspace CAN NET 1, driver 5

Jumper

measuring temeratures, currents of all LV Power Suppies

receive

send

DIP-switch (12bit)

DIO8_1 (1 modul 8bit)

0x184

0x204

0x604

Before using a new DIO-8 module, you have to progam it:

1.) set DIP-switch to 604h (125 kB/sec, address 4)
 

thy module shall only send data after receiving data at 204h
2.) send: addr=604h; len=8; data= 2B,F1,5F,00,00,00,00,00

store data in EEprom
3.) send: addr=604h; len=8; data= 2F,10,10,01,73,61,76,65

 

receive Channel
1 & 2

receive channel
3 & 4

High / Low
Switch

CBX-AI420_1 (4 inputs, 1 module 20bit)

0x291

0x391

0 / 1

CBX-AI420_2 (4 inputs, 1 module 20bit)

0x292

0x392

0 / 2

CBX-AI420_3 (4 inputs, 1 module 20bit)

0x293

0x393

0 / 3

Before using a new CBX-AI420 module, you have to progam it:

1.) set DIP-switch to 0/1 (address 1)
 

thy module shall only send data after a SYNC-signal at address 80h
2.) send: addr=601h; len=8; data= 2F,01,18,02,01,00,00,00
3.) send: addr=601h; len=8; data= 2F,02,18,02,01,00,00,00

store data in EEprom
4.) send: addr=601h; len=8; data= 2F,10,10,01,73,61,76,65

Device

Addressspace CAN NET 0, driver 1&2

Jumper (0=Jumper)

HV Power Supplies

1) normal

2) normal

3) extend

4) extend

A5

A4

A3

A2

A1

A0

Iseg HV_1

0x300

0x301

0x302

0x303

1

0

0

0

0

0

Iseg HV_2

0x308

0x309

0x30A

0x30B

1

0

0

0

0

1

Iseg HV_3

0x310

0x311

0x312

0x313

1

0

0

0

1

0

Iseg HV_4

0x318

0x319

0x31A

0x31B

1

0

0

0

1

1

Iseg HV_5

0x320

0x321

0x322

0x323

1

0

0

1

0

0

Iseg HV_6

0x328

0x329

0x32A

0x32B

1

0

0

1

0

1

Iseg HV_7

0x330

0x331

0x332

0x333

1

0

0

1

0

1

Iseg HV_8

0x338

0x339

0x33A

0x33B

1

0

0

1

0

1

Iseg HV_9

0x340

0x341

0x342

0x343

1

0

0

1

0

1

Iseg HV_10

0x348

0x349

0x34A

0x34B

1

0

0

1

0

1

PVSS Settings

Addr

SubIdx

Driver

Type

Direction

dataIn

1)

0

1

noSpec

IN

dataOutEven

1)

0

2

noSpec

OUT

dataOutOdd

2)

0

1

noSpec

OUT

dataInExtend

3)

0

1

noSpec

IN

dataOutEvenExtend

3)

0

2

noSpec

OUT

dataOutOddExtend

4)

0

1

noSpec

OUT

Device

Addressspace CAN NET 1, driver 6

Siemens S5 to CAN interface

send

receive1

receive2

receive3

CSC595/2 CAN

0x400

0x401

0x402

0x403

Device

Addressspace CAN NET 0, driver 4

Low Voltage Power Supplies (Zentro)

send

receive

PS_1 (+6.5V)

0x500

0x501

PS_2 (-6.5V)

0x502

0x503

PS_3 (+6.0V) (together with PS_4 = +12V)

0x504

0x505

PS_4 (+6.0V) (together with PS_3 = +12V)

0x506

0x507

Device

Addresspace CAN NET 1, driver 3

CMB boards for LED Pulser, temperature reading, pulser steering

dataOut

dataIn

Jumper (0=ON)

CMB_1

0x502

0x503

0x01

CMB_2

0x504

0x505

0x02

CMB_3

0x506

0x507

0x03

CMB_4

0x508

0x509

0x04

CMB_5

0x50A

0x50B

0x05

CMB_6

0x50C

0x50D

0x06

CMB_7

0x50E

0x50F

0x07

CMB_8

0x510

0x511

0x08

CMB_9

0x512

0x513

0x09

CMB_10

0x514

0x515

0x0A

CMB_11

0x516

0x517

0x0B

CMB_12

0x518

0x519

0x0C

CMB_13

0x51A

0x51B

0x0D

CMB_14

0x51C

0x51D

0x0E

CMB_15

0x51E

0x51F

0x0F

CMB_16

0x520

0x521

0x10

CMB_17

0x522

0x523

0x11

CMB_18

0x524

0x525

0x12

CMB_19

0x526

0x527

0x13

CMB_20

0x528

0x529

0x14

CMB_21

0x52A

0x52B

0x15

CMB_22

0x52C

0x52D

0x16

CMB_23

0x52E

0x52F

0x17

CMB_24

0x530

0x531

0x18

CMB_25

0x532

0x533

0x19

CMB_26

0x534

0x535

0x1A

CMB_27

0x536

0x537

0x1B

CMB_28

0x538

0x539

0x1C

CMB_29

0x53A

0x53B

0x1D

CMB_30

0x53C

0x53D

0x1E

CMB_31

0x53E

0x53F

0x1F

CMB_32

0x540

0x541

0x20

CMB_33

0x542

0x543

0x21

CMB_34

0x544

0x545

0x22

CMB_35

0x546

0x547

0x23

CMB_36

0x548

0x549

0x24

CMB_37

0x54A

0x54B

0x25

CMB_38

0x54C

0x54D

0x26